Moxa  Mfg Mini-Store

CANbus to fiber converter, multi-mode, ST connector, 0 to 60°C

Product Page @ Moxa Site MOXA Major Lines
Mfg Part Number:  ICF-1170I-M-ST  
Image may not reflect the actual item.
Price: $491.14
Quantity:
In Stock: 4
No Sales Tax except these states
, PO and Wire.

The ICF-1170I series CANbus-to-fiber converters are used to convert CAN signals from copper to optical fiber. The converters come with 2 KV optical isolation for the CANbus system and dual power inputs with alarm contact relay to ensure that your CANbus system will remain online.

  • Transmits up to 2 km over optical fiber
  • Converts CAN signals to fiber and fiber to CAN signals
  • Baudrate up to 1 Mbps
  • Dual power inputs for redundancy
  • DIP switch for 120 Ω terminal resistance
  • DIP switch for fiber test mode
  • LEDs for Fiber TX, Fiber RX, Power 1, Power 2
  • Wide temperature model available for -40 to 85°C environments
  • Fully compatible with the ISO 11898 standard
CAN Communication
CANbus Interface ISO 11898-2, Terminals (CAN_H, CAN_L,CAN_
GND)
Protocols CAN 2.0A and 2.0B (ISO 11898-2)
Connector Type 3-pin removable screw terminal x1
Termination Resistor Dip switch selector for 120 ? terminal resistor
Buadrate Up to 1 Mbps
System Delay 150 ns
Isolation Protection 2 KV
Transmission Distance Max 2 km (depends on the data rate and the
protocol used)
LED Indicators PWR1, PWR2, Fiber TX, Fiber RX
Note The transmission distance is limited by the signal rate, as mentioned in the ISO 11898-2 standard
Fiber Communication
Connector Type ST (multi-mode) fiber ports x 2
Support Cable 50/125, 62.5/125, or 100/140 ?m (multi-mode)
Wavelength 850 nm
Tx Output Multi-mode (> -5 dBm)
RX Sensitivity Multi-mode (-20 dBm)
Physical Characteristics
Housing Aluminum (1 mm)
Dimensions 30.3 x 70 x 115 mm (11.9x27.6x45.3 in)
Environmental Limits
Operating Temperature Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 85°C (-40 to 185°F)
Operating Humidity 5 to 95% RH
Storage Temperature -40 to 85°C (-40 to 185°F)
Power Requirements
Input Voltage 12 to 48 VDC dual power inputs for redundant power
Power Consumption ICF-1170I: 221 mA @ 12 V
Alarm Contact: 1 relay output with current carrying of 1 A @ 24 VDC
Voltage Reversal Protection Protects against V+/V- reversal
Over Current Protection 1.1 A (protects against two signals shorted together)
Regulatory Approvals
EMI EN55022 1998, Class A
EMS EN61000-4-2 (ESD), Criteria B, Level 4
EN61000-4-3 (RS), Criteria A, Level 2
EN61000-4-4 (EFT), Criteria B, Level 4
EN61000-4-5 (Surge), Criteria B, Level 2
EN61000-4-6 (CS), Criteria B, Level 2
En61000-4-8 (PFMF), Criteria A, Level 3
UL/CUL UL-508
TUV EN 60950-1
CE Class A
FCC Part 15 sub Class A
Freefall IEC 60068-2-32
MTBF 792085 hrs
Warranty
Warranty Period 5 years

Specification

Power Requirements
Power Consumption ICF-1170I: 221 mA @ 12 V 
Alarm Contact: 1 relay output with current carrying of 1 A @ 24 VDC
Input Voltage 12 to 48 VDC dual power inputs for redundant power
Voltage Reversal Protection Protects against V+/V- reversal
Over Current Protection 1.1 A (protects against two signals shorted together)
Fiber Communication
Wavelength 850 nm
Rx Sensitivity Multi-mode (-20 dBm)
Connector Type ST (multi-mode) fiber ports
TX Output Multi-mode (> -5 dBm)
Support Cable 50/125, 62.5/125, or 100/140 μm (multi-mode)
Environmental Limits
Operating Temperature Standard Models: 0 to 60°C (32 to 140°F) 
Wide Temp. Models: -40 to 85°C (-40 to 185°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)
MTBF (mean time between failures)
Time 792,085 hrs
Database Telcordia (Bellcore), GB
CAN Communication
Note The transmission distance is limited by the signal rate, as indicated in the ISO 11898-2 standard.
Transfer Rate Up to 1 Mbps
Protocols CAN 2.0A and 2.0B (ISO 11898-2)
Isolation Protection 2 KV
Transmission Distance Max 2 km (depends on the data rate and the protocol used)
System Delay 150 ns
Connector Type 3-pin removable screw terminal x1
ESD Protection Supports 15 KV
LED Indicators PWR1, PWR2, Fiber TX, Fiber RX
CAN Interface ISO 11898-2, Terminals (CAN_H, CAN_L,CAN_GND)
Termination Resistor Dip switch selector for 120 Ω terminal resistor
Physical Characteristics
Weight Product only: 175 g (0.39 lb) 
Packaged: 320 g (0.71 lb)
Dimensions 30.3 x 70 x 115 mm (1.19 x 2.76 x 4.53 in)
Housing Aluminum (1 mm)
Standards and Certifications
EMI EN 55022 Class A, FCC Part 15 Subpart B Class A
Safety UL 508, EN 60950-1
EMS EN 61000-4-2 (ESD) Level 4,
EN 61000-4-3 (RS) Level 2,
EN 61000-4-4 (EFT) Level 4,
EN 61000-4-5 (Surge) Level 3,
EN 61000-4-6 (CS) Level 2,
EN 61000-4-8 (PFMF) Level 3
EMC CE, FCC
Freefall IEC 60068-2-32
Green Product RoHS, CRoHS, WEEE
Warranty
Warranty Period 5 years
Details See http://www.moxa.com/support/warranty.htm

If you need accessory information for this product, please use our Online Contact Us Form to reach us, our industrial sales team is here to help you find the accessories.