Power Requirements | |
Power Consumption | 118 mA @ 24 VDC |
Power Input | 24 VDC nominal, 12 to 36 VDC |
Thermocouple Input | |
Input Impedance | 10M ohms |
Sampling Rate | 12 samples/sec (all channels) |
Resolution | 16 bits |
Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C |
Millivolt Type | • Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV • Fault and over-voltage protection: -35 to +35 VDC (power off); -25 to +30 VDC (power on) |
Sensor Type | J, K, T, E, R, S, B, N |
Inputs and Outputs | |
Thermocouple Inputs | 8 channels |
LAN | |
Protection | 1.5 KV magnetic isolation |
Ethernet | 2 x 10/100 Mbps switch ports, RJ45 |
Protocols | Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP |
Environmental Limits | |
Operating Temperature | Standard Models: -10 to 60°C (14 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
MTBF (mean time between failures) | |
Time | 631,418 hrs |
Database | Telcordia (Bellcore) |
Physical Characteristics | |
Weight | under 200 g |
Dimensions | 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in) |
Wiring | I/O cable max. 14 AWG |
Standards and Certifications | |
EMI | FCC Part 15 Subpart B Class A |
Safety | UL 508 |
Shock | IEC 60068-2-27 |
Vibration | IEC 60068-2-6 |
EMS | IEC 61000-4, IEC 61000-6 |
Freefall | IEC 60068-2-32 |
Warranty | |
Warranty Period | 5 years |
Details | See www.moxa.com/warranty |